Modbus Router convert Modbus data between Modbus RTU and Modbus TCP protocols, this allows devices and systems using different Modbus protocols to communicate. Modbus Router

  1. Enable/Disable Modbus Router feature
  2. configure the mode, options Modbus RTU to Modbus TCP, and Modbus TCP to Modbus RTU
    1. Modbus RTU to Modbus TCP refers the RTU side as Modbus slave, while TCP side as Modbus master
    2. Modbus TCP to Modbus RTU refers the TCP side as Modbus slave, while RTU side as Modbus master
  3. Configure the Modbus TCP side settings, including IP address and port
  4. Configure the BModbus RTU side settings, including serial COM interface, Baudrate, Data bit, Stop bit, Parity.